Overview
The Johnson Controls VG1241AF+9T4AGA is a high-performance valve and actuator assembly that combines a 1/2-inch, 2-way forged brass ball valve with a VA9104-AGA-3S non-spring return electric actuator. Designed for commercial HVAC and building automation systems, this direct-coupled assembly provides precise control of hot water, chilled water, and glycol solutions. Operating on a 24 VAC supply, it utilizes floating control without timeout to accurately position the valve, and its non-spring return design ensures the valve maintains its last position upon a loss of power.
Features
- Long operational lifespan with a minimum life expectancy of 200,000 full leak-free cycles.
- Non-spring return design that holds the valve’s position in place during power interruptions.
- Direct-coupled mounting configuration for quick, tool-free field installation.
- Integrated manual override handle to assist with commissioning, testing, or emergency adjustments.
- Equal percentage flow characteristic for stable and accurate modulation matching traditional globe valves.
- NEMA 2 rated actuator enclosure providing protection against dripping water and electrical hazards.
Specifications
- Valve Size: 1/2 inch FNPT
- Valve Type: 2-way ball valve
- Flow Coefficient (Cv): 2.9
- Actuator Model: VA9104-AGA-3S
- Supply Voltage: 24 VAC, 50/60 Hz
- Control Type: Floating (without timeout) or Two-Position
- Output Torque: 35 lb-in (4 N·m)
- Full Stroke Travel Time: 60 seconds
- Maximum Close-off Pressure: 200 psid (1378 kPa)
- Maximum Body Pressure Rating: 580 psig (3996 kPa), PN40
- Materials of Construction: Forged brass body, chrome-plated brass ball, nickel-plated brass stem, EPDM O-ring stem seals, and graphite-reinforced PTFE seats
- Fluid Temperature Range: 23°F to 203°F (-5°C to 95°C)
- Electrical Termination: Screw terminals
Applications
- Hydronic heating and cooling control loops in commercial environments.
- Chilled and hot water coil management in air handling units (AHUs) and fan coil units (FCUs).
- Automated temperature control in building management and energy optimization systems.
- Closed-loop water distribution networks utilizing up to a 50% industrial glycol solution.