Overview
The Fireye BP110UVFR-S5M is a compact, microprocessor-based BurnerPRO primary flame safeguard control system designed for single-burner commercial heating and process applications. This system manages burner sequencing, ignition, and continuous flame monitoring for burners firing oil or gas fuels. It features a Modbus RTU interface for reading status and writing custom timing parameters. As a Series 5 model, it is specifically designed for functionality compatible with Siemens LFL wiring bases, making it an ideal solution for both new installations and retrofitting existing plants.
Features
- Dual built-in amplifiers supporting UV only, FR only, or combined UV+FR flame monitoring applications.
- Modbus RTU communication via RS-485 for remote monitoring and parameter configuration.
- Seven SMART LEDs providing real-time operating status and diagnostic lockout information.
- Run/Check feature allowing operators to pause the program sequence for system troubleshooting.
- Non-volatile lockout capability ensuring safety information is retained during power loss.
- Air-flow proving and integrated valve proving (VP) functionality to check for leaks before startup.
- Compatible with UV90L, UV1AL, and UV5 scanners for ultraviolet flame detection.
Specifications
- Model: BP110UVFR-S5M
- Supply Voltage: 110 VAC (+20%, -15%) at 50/60Hz
- Power Consumption: 7 VA
- Temperature Rating: Operating range of -40 degrees C to +60 degrees C (-40 degrees F to 140 degrees F)
- Protection Category: IP40
- Humidity: 90 percent relative humidity (non-condensing)
- Timing: Series 5 pre-programmed operational timings
- Interface: RJ-45 connector for Modbus A+ and B- connections
- Weight: Approximately 2.5 lbs (1.13 kg)
Applications
The BP110UVFR-S5M is utilized in commercial and industrial combustion systems for on-off, multi-stage, or modulating burners. It is suitable for steam or hot water generating boilers and process equipment. Because the FR amplifier circuitry is self-checking, it can be used in applications requiring continuous burner operation (longer than 24 hours). When used in UV-only mode, it is intended for intermittent operation where the burner cycles at least once every 24 hours. Its design allows for direct replacement of common LFL or TMG automatic burner controllers.