Overview
The Fireye SB560522AA is a compact, microprocessor-based modular flame safeguard control designed for the automatic ignition and continuous flame monitoring of commercial heating and process equipment. As part of the SB Series, it serves as a professional-grade burner management solution that ensures safe combustion cycles for various fuel types, including gas, oil, or combination burners. This specific model is a direct drop-in replacement for retired Eclipse VeriFlame burner systems, utilizing the same wiring subbase to simplify field upgrades and replacements.
Features
- Ultraviolet (UV) flame detection for accurate and reliable sensing across various burner types.
- Selectable integrated purge control to clear the combustion chamber before ignition.
- 10/15 second Trial for Ignition (TFI) for dependable sequencing.
- Modular design with a compact footprint, tested to EN298 standards.
- LED indicators on the front panel provide real-time operating status and lockout alarms.
- Integrated test jack for real-time flame signal readings and connection to alphanumeric displays.
- Push-button reset for lockout conditions and pilot turndown testing.
- Pre-purge air check and reset on power functionality.
Specifications
- Model Number: SB560522AA
- Input Voltage: 120 VAC (102V min, 132V max), 50/60 Hz
- Power Consumption: 12VA internal consumption
- Flame Detection: UV (Ultraviolet)
- Trial for Ignition (TFI): 10/15 seconds
- Operating Temperature: -40 degree F to 140 degree F (-40 degree C to 60 degree C)
- Shipping Weight: Approximately 3 lbs (1.4 kg)
- Approvals: UL Listed, FM Approved, and tested to EN298
Applications
The SB560522AA is ideally suited for industrial boilers, commercial burner systems, and various combustion equipment where precision flame supervision is critical. It is commonly used in power plants, pulp and paper mills, and food processing facilities. Because it uses the same wiring subbase as the Honeywell Eclipse VeriFlame system, it is frequently employed as a direct replacement in existing installations requiring updated microprocessor-based safety controls.



Reviews
There are no reviews yet.