Overview
The Siemens LME71.112A1PKG-PRG1 is a microprocessor-based flame safeguard assembly designed for the supervision of 1- or 2-stage gas forced draft burners in intermittent operation. This specific package includes the LME71.000A1 base unit pre-programmed with the PME71.112A1 program module and includes the AGG3.710 connector plug set. Unlike other variants, the 112A1 configuration is specifically designed for applications requiring burner control without a purge cycle. It provides critical safety functions by managing the startup and operation of the burner, energizing safety shutoff valves, and monitoring the flame to ensure safe combustion.
Features
- Digital signal handling for accurate control sequences and timing
- Integrated BC interface for connecting external displays (AZL2) or PC software
- Multicolor LED signal lamp provides status notifications for operations, recycles, and faults
- Proof of Closure (POC) input allows for monitoring the gas valve position to ensure it is 100% closed
- Air pressure supervision with a function check of the air pressure switch during startup and operation
- Electrical remote lockout reset facility and undervoltage detection
- Compatible with ionization probes or UV flame detectors (such as QRA2, QRA4.U, or QRA10)
- Lockout reset button (info button) located directly on the unit
Specifications
- Model: LME71.112A1PKG-PRG1
- Base Unit: LME71.000A1
- Program Module: PME71.112A1 (Basic flame safeguard without purge)
- Mains Voltage: AC 120 V (50/60 Hz)
- Power Consumption: Approximately 12 VA
- Safety Class: I
- Degree of Protection: IP40 (when mounted)
- Operating Temperature: -20 C to +60 C
- Weight: Approximately 1.1 lbs to 1.2 lbs (Base unit only); Package weight approx. 2.0 lbs
- Approvals: UL, FM, CSA, and CE
Applications
- Supervision of medium to high capacity gas forced draft burners
- Industrial thermal process applications requiring 1- or 2-stage burner control
- Atmospheric burners of medium to large capacity
- HVAC and boiler systems where a non-purge startup sequence is required
- Monitoring flames via ionization rod or UV scanner in gas-fired equipment



Reviews