BurnerPRO Single Burner Control, 230VAC 50/60Hz, Series 1 timings, with UV non-self check amplifier, IP40. Compatible with 60-2981-1 and Siemens LFL wiring base
Overview
The Fireye BP230UV-S1 Burner Control is a compact, microprocessor-based primary flame safeguard control system designed for single burner commercial heating and process equipment. It provides the necessary burner sequencing, automatic ignition, and continuous flame monitoring for on-off, multi-stage, or modulating burners firing oil and gas fuels. This model operates on 230VAC 50/60Hz, utilizes a UV non-self-check amplifier, and uses Series 1 timings. It is engineered for non-permanent operations requiring the burner to recycle at least once every 24 hours, and it is a plug-and-play functional replacement for select Siemens LFL control models like the LFL1.322.
Features
- Microprocessor-based control system.
- Non-volatile lockout capability.
- High capacity relay contacts.
- Proof of fuel valve closure (POC).
- Air-flow proving.
- A Run/Check feature allowing the operator to pause the program sequence for system troubleshooting.
- Remote and local reset capabilities.
- One-second Flame Failure Response Time (FFRT).
- Seven SMART LEDs for on-board diagnostic lockout information and current operating status.
- Real-time internal diagnostics for enhanced safety integrity.
- Extended temperature operation with an over-temp inhibit feature.
Specifications
- Model: BP230UV-S1
- Type: Single Burner Control, Primary Flame Safeguard
- Supply Voltage: 230 VAC (+10%, -15%) 50/60Hz
- Power Consumption: 7 VA
- Flame Amplifier: UV Non-Self Check
- Timings: Series 1 timings
- Protection Category: IP40 (except wiring base)
- Operating Temperature Range: -40°C to +60°C (-40°F to 140°F)
- Compatibility: Fireye 60-2981-1 wiring base and is functionally compatible with Siemens LFL wiring base (LFL1.322) with UV flame scanners.
Applications
- Provides proper burner sequencing, ignition, and continuous flame monitoring in commercial heating and process equipment.
- Suitable for on/off, multi-stage, or modulating burners used in small to medium-sized boilers for steam or hot water generation.
- Controls equipment firing natural gas, light oil, or other fuels where UV flame detection is appropriate.
- Ideal for retrofit applications to replace obsolete Siemens LFL controls.


Reviews