Overview
The Fireye BurnerPRO BP110UVFR-SXMP is a compact, microprocessor-based primary flame safeguard control system. It is designed to provide proper burner sequencing, ignition, and continuous flame monitoring for commercial heating and process equipment firing oil or gas fuels. This Flexible Series (SX) model features Modbus communication and integrated valve proving, offering a modern, non-volatile electronic replacement for older electro-mechanical designs like the Siemens LFL. It utilizes two built-in amplifiers to support both ultraviolet (UV) and flame rod (FR) detection, ensuring reliable operation and safety self-testing on every start.
Features
- Microprocessor-based control for high accuracy and reliability with non-volatile lockout capability.
- Dual built-in amplifiers (UV and FR) allow for flexible flame monitoring configurations.
- Integrated Modbus RTU communication via an RJ45 jack for remote monitoring and data access.
- Valve proving feature checks for leakage through safety shutoff valves during start-up or after shutdown.
- Seven or eight Smart LEDs provide real-time diagnostic information, flame quality, and lockout reasons.
- Flexible Series timings (SX) designed for specific industrial burner requirements.
- Run/Check feature allows operators to stop the program sequence at specific points (Purge, Ignition, etc.) for troubleshooting.
- Safety self-test performed automatically on every start cycle.
Specifications
- Model Number: BP110UVFR-SXMP
- Supply Voltage: 110 VAC (+20%, -15%) 50/60 Hz
- Power Consumption: 7 VA
- Operating Temperature: -40 degree F to 140 degree F (-40 degree C to +60 degree C)
- Humidity: 90% RH (Non-condensing)
- Protection Category: IP40 (indoor use)
- Flame Failure Response Time (FFRT): Typically 1 or 3 seconds depending on configuration
- Weight: Approximately 2.5 lbs (1.13 kg)
- Compatibility: Compatible with 60-2981-1 and Siemens LFL wiring bases
Applications
The BurnerPRO BP110UVFR-SXMP is ideally suited for managing on-off, multi-stage, or modulating burners in various industrial and commercial environments. Typical applications include process burners, pilot burners, duct burners, and industrial gas burners. It is commonly used in boiler operations, kiln firing, heat treatment, refinery applications, and waste gas units. It is designed for non-permanent operation when using a UV scanner (requiring a recycle every 24 hours) and can support permanent operation when used with a flame rod.