BurnerPRO Single Burner Control, 110VAC 50/60Hz, Series 2 timings, with UV non-self check amplifier, IP40. Compatible with 60-2981-1 and Siemens LFL wiring base
Overview
The Fireye BP110UV-S2 is a compact, microprocessor-based BurnerPRO Single Burner Control that serves as a primary flame safeguard system for commercial heating and process equipment. It provides proper burner sequencing, automatic ignition, and continuous flame monitoring for single on-off, multi-stage, or modulating burners firing oil and gas fuels. This specific model operates on 110VAC 50/60Hz power and utilizes Series 2 factory-set operational timings.
Features
- Microprocessor-based integrated burner management control.
- Uses a built-in UV non-self check amplifier for flame monitoring.
- Designed for use in non-permanent operations requiring burner recycle at least once every 24 hours.
- Seven SMART LEDs provide real-time operating status and diagnostic lockout information.
- Includes expanded functions such as non-volatile lockout capability, proof of fuel valve closure, air-flow proving, and a run/check feature.
- One second flame failure response time for enhanced safety.
- Allows for remote and local reset.
Specifications
- Model: BP110UV-S2
- Supply Voltage: 110 VAC (50/60Hz)
- Timings: Series 2 timings
- Flame Amplifier: UV non-self check
- Protection Category: IP40
- Power Consumption: 7 VA
- Compatibility: Fireye 60-2981-1 and Siemens LFL wiring bases
Applications
- Single burner commercial heating equipment.
- Process equipment and industrial boilers firing oil and gas fuels.
- Retrofit solution, particularly for replacing the Siemens LFL1.333-110V control.
- Suitable for various combustion systems including process burners, pilot burners, and duct burners.