Overview
The Fireye YB230UVSC is a microprocessor-based BurnerLogiX Y-Series chassis and flame amplifier module designed for integrated burner management. This sophisticated control system provides essential burner sequencing, ignition, and flame monitoring protection for automatically ignited oil, gas, and combination fuel burners. As part of the BurnerLogiX family, the YB230UVSC ensures safe burner operation by coordinating the burner/blower motor, ignition, and fuel valves while providing real-time status through SMART LEDs.
Features
- UV Self-Check Capability: Includes an integrated amplifier module designed specifically for use with self-checking ultraviolet flame scanners to enhance system reliability.
- Non-Volatile Memory: Retains current operating status, internal history, and lockout information even if power is interrupted.
- Run/Check Switch: Allows operators to stop the program sequence in four different positions (Purge, PTFI, MTFI, or Auto) for easier system testing.
- Advanced Diagnostics: Features SMART LEDs for status indication and supports optional VFD or LCD displays for full language descriptors of lockout information.
- Communication Options: Supports Modbus communications via an RS485 multi-drop link for integration with building management systems.
- Robust Protection: Provides NEMA 4x (IP66) protection when displays are mounted remotely.
Specifications
- Model Number: YB230UVSC
- Supply Voltage: 230 VAC (+10%, -15%) at 50/60 Hz
- Power Consumption: 25 VA
- Temperature Rating: -40 degree F to 140 degree F (-40 degree C to +60 degree C)
- Protection Category: NEMA 1 (IP01) for the chassis
- Shipping Weight: Approximately 3.2 lbs (1.45 kg)
- Dimensions: 4.00 x 5.00 x 2.12 inches
- Approvals: FM and CE Approved
Applications
The YB230UVSC is primarily used in commercial and industrial HVAC and process industries to manage automatically ignited burners. It is designed to work with various Fireye components, including YP programmer modules and self-checking ultraviolet scanners. Common applications include the supervision of gas-fired or oil-fired flames where a self-checking UV system is required for continuous operation or enhanced safety protocols.