Overview
The Johnson Controls T-5210-1001 is a direct-acting pneumatic temperature transmitter designed to measure temperature and convert it into a proportional air pressure signal. This signal is transmitted to pneumatic receivers, controllers, or receiver-indicators within commercial and industrial HVAC systems. It incorporates pneumatic feedback to ensure an exact proportional relationship between the measured temperature and the transmitted signal, and features a bimetal element to compensate for ambient temperature effects.
Features
- Direct-acting pneumatic temperature transmitter with a remote copper bulb sensing element.
- Incorporates pneumatic feedback for high linearity and an exact proportional relationship between measurement and signal.
- Features a ball-type control port for increased accuracy and a reinforced lever for enhanced linearity.
- Built-in bimetal element compensates for ambient temperature effects.
- Includes an integral hypodermic needle test point for straightforward calibration check and verification.
Specifications
- Operating Temperature Range: 50 to 100°F (10 to 38°C)
- Element Temperature Range: -40 to 230°F
- Capillary Length: 5-1/2 inch (140 mm) copper capillary
- Output Pressure Range: 3 to 15 psig
- Supply Pressure: 20 psig nominal (25 psi maximum)
- Air Consumption: 45 SCIM (Standard Cubic Inches per Minute)
- Restriction Requirement: Requires a 0.007 inch restricted supply
Applications
- Commercial building HVAC pneumatic control systems
- Air handling unit (AHU) temperature sensing and control
- Industrial process temperature monitoring
- Integration into legacy pneumatic control panels and DDC systems


Reviews