Overview
The Fireye SB560532AB is a compact, microprocessor-based modular burner management system within the SB Series. It is designed to provide automatic ignition and continuous flame monitoring for commercial-sized heating and process equipment. As a direct drop-in replacement for the retired Honeywell Eclipse VeriFlame system, this control unit integrates digital logic and analog measuring circuitry to manage burner sequences and monitor flames for gas, oil, or combination burners. This specific model features a no-purge sequence with a manual reset requirement following a safety lockout.
Features
- Modular, compact design for easy installation and maintenance.
- Microprocessor-based technology for reliable burner sequencing and flame monitoring.
- Plug-in design compatible with open and closed wiring bases.
- LED indicator lights on the front panel provide real-time operating and alarm status.
- Integrated test jack for real-time flame signal strength readings and connection to remote displays.
- Manual reset push button to clear lockout conditions and initiate check cycles.
- Direct drop-in replacement for Honeywell Eclipse VeriFlame burner controls.
- Certified to EN298 standards, UL Listed, and FM Approved.
Specifications
- Model Number: SB560532AB
- Supply Voltage: 120 VAC (min. 102, max. 132), 50/60 Hz
- Power Consumption: 12 VA
- Trial for Ignition (TFI): 10/15 seconds
- Purge Type: No purge
- Amplifier Type: UV (Ultraviolet)
- Reset Type: Manual reset
- Operating Temperature: -40 degree F to 140 degree F (-40 degree C to 60 degree C)
- Shipping Weight: Approximately 3 lbs (1.4 kg)
- Compatible Scanners: UV1A, UV2, UV8A, 45UV3, UV90, and 45UV5 series
Applications
The SB560532AB is utilized in commercial and industrial combustion systems to manage single gas, oil, or combination gas/oil burners. It is commonly applied in sectors such as power generation, petrochemical processing, pulp and paper manufacturing, and metal production. It is ideally suited for heating and process equipment where a no-purge startup sequence is required and manual intervention is preferred for safety resets.