Overview
The Fireye SB560242XA is a compact, microprocessor-based modular burner management system from the SB Series, designed to provide automatic ignition and continuous flame monitoring for commercial-sized heating and process equipment. This specific model serves as a direct drop-in replacement for the retired Honeywell Eclipse VeriFlame burner control system (model VF560242XA). It integrates essential digital logic and analog measuring circuitry to manage burner sequences and ensure safety by monitoring for the presence of a flame across various fuel types, including gas and oil.
Features
- Modular, compact design facilitates easy installation and maintenance.
- Integrated LED indicator lights provide real-time operating status and coded lockout alarm sequences for troubleshooting.
- Features a sequence hold capability and a reset function that triggers on power application.
- Includes a recessed test jack for real-time flame signal intensity readings and connection to an alpha-numeric display.
- Supports multiple flame sensor options, specifically configured for Ultraviolet (UV) amplifiers in this model.
- Designed with a plug-in architecture compatible with open and closed wiring bases.
Specifications
- Model Number: SB560242XA
- Input Voltage: 120 VAC (102 min to 132 max), 50/60 Hz
- Trial for Ignition (TFI): Selectable 5 or 10 seconds
- Control Mode: Modulating (air damper control)
- Amplifier Type: Ultraviolet (UV)
- Reset Type: Reset on power
- Power Consumption: 12 VA (internal consumption)
- Operating Temperature: -40 degree F to 140 degree F (-40 degree C to 60 degree C)
- Shipping Weight: Approximately 3 lbs (1.4 kg)
- Approvals: Tested to EN298, UL Listed, and FM Approved
Applications
The SB560242XA is primarily used in commercial and industrial combustion systems for the control of single gas, oil, or combination gas/oil burners. It is ideal for heating and process equipment where modulating air damper control is required for optimized burner performance. As a “drop-in” replacement, it is frequently used to modernize existing installations that previously utilized Eclipse VeriFlame controls without requiring extensive rewiring.