The Fireye MP230H is a specialized programmer module designed for use with the Fireye Modular M-Series II flame safeguard control system. It is a plug-in component that defines the operational characteristics of the burner management system, specifically providing 2-stage burner capability. The MP230H is engineered as a direct replacement for the legacy Fireye M3H Series, bringing modern modularity to industrial and commercial combustion applications. It features a series of dipswitches that allow for field configuration of critical timing and operational logic, ensuring the system manages burner sequencing, ignition, and flame monitoring with precision.
Features
- Selectable Purge Timing: Field-adjustable dipswitches allow users to set specific prepurge durations.
- Pilot Stabilization: Includes a dedicated timing period to ensure a stable pilot flame before the main fuel valve is energized.
- Dual Mode Operation: Dipswitch selectable Recycle or Non-Recycle operation in the event of a flame failure.
- User Interface: Integrated LED indicator lights provide real-time status of the control’s operating sequence.
- 2-Stage Capability: Specifically designed to support the sequencing requirements of two-stage burners.
- Easy Installation: Features a rugged plug-in design for quick mounting into the MC120 or MC230 chassis.
Specifications
- Model Number: MP230H
- Compatible Chassis: Fireye Modular M-Series II (MC120, MC230)
- Supply Voltage: 120V AC (Min. 102V, Max. 132V)
- Frequency: 50/60 Hz
- Pilot Trial for Ignition (PTFI): Selectable via dipswitches (typically 5 or 10 seconds)
- Pilot Stabilization Period: 8 seconds
- Flame Failure Response Time (FFRT): Determined by the selection of the associated amplifier module
- Operating Temperature: -40 degree F to 140 degree F (-40 degree C to 60 degree C)
- Replacement For: Fireye M3H Series controls
Applications
The Fireye MP230H is primarily used in industrial and commercial burner management systems that require automatic ignition and continuous flame monitoring. It is specifically suited for two-stage burners firing gas, light oil, or combination fuels. Common applications include heating boilers, process furnaces, and industrial ovens where precise control over purge timing and pilot stabilization is necessary for safe and efficient combustion. It is a critical component for facilities looking to maintain or upgrade existing M-Series II installations.