Overview
The Fireye MEDC2 is a high-performance, plug-in flame amplifier module designed for industrial burner management systems. It is specifically engineered to interface with scanners providing a dry contact output, such as the Fireye Phoenix (85UVF) or InSight series. This module is part of the Fireye MicroM and M-Series II families, providing critical flame supervision to ensure combustion safety by detecting the presence or absence of a flame.
Features
- Dry contact input capability for seamless integration with self-contained flame scanners.
- Ultra-fast 0.3-second Flame Failure Response Time (FFRT) for rapid hazard mitigation.
- Plug-in design allowing for easy installation, maintenance, and replacement within compatible chassis.
- Test jacks provided on the front of the module for real-time flame signal measurement (0-10 VDC).
- Built-in LED indicators to provide clear visual status of the flame signal.
Specifications
- Model Number: MEDC2
- Flame Failure Response Time: 0.3 seconds
- Input Type: Dry Contact
- Operating Voltage: Determined by the compatible MicroM or M-Series II chassis (typically 120V or 230V)
- Operating Temperature: -40 degrees F to 140 degrees F (-40 degrees C to 60 degrees C)
- Shipping Weight: Approximately 1 lb
- Compatibility: Used with MEP237 programmer modules and 85UVF4-1WR, 85IRF4-1QDWR, or InSight scanners
Applications
The MEDC2 is primarily used in commercial and industrial combustion systems where high-speed flame failure detection is required. It is commonly applied in gas and oil burner systems, refinery process heaters, and duct burners. It is specifically designed for systems utilizing Fireye Phoenix or InSight scanners that output a dry contact signal rather than a raw sensor signal.