Overview
The Fireye MECD1 is a plug-in cadmium sulfide flame amplifier module designed for use with the Fireye Modular MicroM series burner management systems. This compact, microprocessor-based module is engineered to provide continuous flame monitoring for commercial-sized heating and process burners. It specifically works in conjunction with cadmium sulfide scanners to detect the presence or absence of a flame, ensuring safe combustion operation.
Features
- Designed specifically for use with the Fireye MicroM chassis and wiring base.
- Features a Flame Failure Response Time (FFRT) of 0.8 seconds for rapid safety shutdown.
- Uniform 0-10 VDC test jacks allow for easy flame signal measurement during operation.
- Plug-in design simplifies installation and maintenance.
- Compatible with cadmium sulfide (cad cell) flame detectors.
- Part of a modular system that allows for flexible configuration of burner control functions.
Specifications
- Model Number: MECD1
- Amplifier Type: Cadmium Sulfide (Cad Cell)
- Flame Failure Response Time (FFRT): 0.8 seconds
- Flame Signal Output: 0-10 VDC via test jacks
- Operating Temperature: -40 F to 140 F (-40 C to 60 C)
- Humidity: 85 percent RH maximum, non-condensing
- Shipping Weight: Approximately 3 lbs (1.4 kg)
- Compliance: UL listed and CSA approved when used with compatible Fireye systems.
Applications
The MECD1 amplifier is used in industrial and commercial combustion systems that utilize Fireye MicroM controls. It is typically paired with the Fireye CS1A5 or Honeywell C554A cadmium sulfide scanners to monitor light oil flames. It is ideally suited for burners that cycle at least once every 24 hours and is commonly found in HVAC systems, process heating, and small-to-medium industrial boilers.