Overview
The Fireye MBCE-230FR-1 is a single-channel flame sensor module designed to provide visual indication and electrical outputs based on the presence of a flame in a combustion chamber. Using the ionization principle, this module works in conjunction with Fireye flame rods to monitor flame presence either independently or as a component within a larger burner management system. It is specifically designed for 230 VAC applications and is CE approved, though it is important to note that this specific model is not for sale in the United States.
Features
- Ionization/Flame Rod Compatibility: Specifically engineered for use with flame rods to sense flame activity.
- LED Indication: Features a built-in LED that provides immediate visual confirmation of the flame ON/OFF status.
- Proportional Signal Output: Includes a 4-20 mA output that allows for direct reading and monitoring of the flame signal strength.
- Self-Checking Technology: Provides a cost-effective, self-checking method to ensure reliable flame monitoring.
- Versatile Mounting: Designed to be used with an 11-pin relay base (60-2886) for easy installation on a DIN rail or panel surface.
- Durable Design: Built to perform in demanding industrial combustion environments.
Specifications
- Model Number: MBCE-230FR-1
- Supply Voltage: 230 VAC (+10%, -15%), 50/60 Hz
- Power Consumption: 0.1 Amp
- Flame Failure Response Time (FFRT): 1 second
- Flame Relay Output: SPDT 1 Amp Resistive @ 230 VAC / 1 Amp @ 30 VDC
- Analog Output: 4-20 mA DC proportional to flame strength
- Operating Temperature: -40°F to 150°F (-40°C to 65°C)
- Humidity: 85% RH maximum, non-condensing
- IP Rating: IP20
- Agency Approvals: CE / EN298:2012
- Shipping Weight: Approximately 1 lb (0.5 kg)
Applications
The MBCE-230FR-1 is ideal for industrial and commercial burner management and flame safeguard systems. It is primarily used in natural gas applications but can also be adapted for propane and light fuel oil systems. The module is intended for non-permanent operation where the burner is recycled at least once every 24 hours. Common applications include boiler controls, furnaces, and other combustion equipment where reliable flame rectification sensing is required.