Overview
The Siemens LME75.811A1PKG-PRG3 is a comprehensive burner control package designed for the commissioning and supervision of 1-stage or modulating forced draft burners. This microprocessor-based flame safeguard is specifically engineered for continuous operation, exceeding 24 hours of uninterrupted use. The “PKG” designation indicates a pre-assembled convenience kit that includes the LME75.000A1 base unit, the PME75.811A1 program module, and a complete AGG3.710 connector plug set. It is ideal for medium to large-capacity industrial and commercial burners, providing advanced safety functions such as integrated valve proving and linkageless fuel-air ratio control when paired with Siemens SQM actuators.
Features
- Designed for continuous operation (> 24 hours) for high-demand industrial applications
- Integrated valve proving (leakage test) function to ensure fuel train integrity
- Compatible with self-checking UV scanners (QRA7), infrared scanners (QRI), or ionization probes
- 3-color LED signal lamp and 3×7-segment display for clear operating status, service information, and fault diagnostics
- Programmable actuator modulation via PWM, analog (DC 0…10 V, 4…20 mA), or 3-position step control
- Digital signal handling ensures accurate control sequences and repeatable performance
- BC interface allows for direct connection of an AZL2 display unit or PC for parameterization
- Safety-critical design meeting SIL3 classification (DIN EN 13611) for high-level protection
Specifications
- Model: LME75.811A1PKG-PRG3
- Operating Voltage: AC 120 V (+10% / -15%)
- Mains Frequency: 50…60 Hz
- Power Consumption: Approximately 12 VA
- Protection Rating: IP40 (when mounted)
- Operating Temperature: -20 C to +60 C
- Safety Level: SIL3 Capable; designed for 250,000 startup cycles (approx. 10 years)
- Dimensions: 12 x 8 x 8 inches (packaged)
- Weight: Approximately 5 lbs
Applications
- Supervision of 1-stage or modulating forced draft burners for gaseous and liquid fuels
- Industrial thermoprocessing plants complying with EN 746-2 requirements
- Continuous operation burner systems such as steam boilers, thermal oil heaters, and industrial furnaces
- Linkageless burner systems requiring integrated valve proving and precise actuator control
- Replacement of legacy burner controls in existing medium to large-capacity combustion plants