Overview
The Siemens LME39.400C2 is a sophisticated, microprocessor-based burner control designed for the startup and supervision of 1- or 2-stage gas or oil burners of small to medium capacity. Engineered for intermittent operation, this controller provides high-precision program sequences through digital signal handling and is primarily intended for integration by original equipment manufacturers (OEMs). It features a grey plastic housing and utilizes a Burner Communication Interface (BCI) for parameterization and diagnostics, making it a versatile component for modern combustion and thermal process plants.
Features
- Microcomputer-controlled program sequences ensure high accuracy and repeatability
- Parameterizable via BCI interface using AZL2 display or ACS410 software for customized burner sequences
- Integrated undervoltage detection and air pressure supervision with functional checks during startup and operation
- Multicolor LED indicator provides clear visual messages for operational status and detailed fault diagnostics
- Electrical remote reset facility allows for efficient system management from a distance
- Automatic controlled intermittent operation triggers a safety shutdown and restart after 24 hours of continuous run time
- Robust safety design includes limitation of the number of repetitions and a designed lifetime of 250,000 startup cycles
Specifications
- Model: LME39.400C2
- Supply Voltage: AC 230 V (50/60 Hz)
- Power Consumption: 12 VA
- Waiting Time (tw): Max 2.5 s
- Safety Time (TSA): Max 5 s
- Preignition Time (t3): Approx 3 s
- Postignition Time (t3n): Approx 4 s
- Purge Time (t1′): 14.5 s
- Protection Rating: IP40 (when installed)
- Operating Temperature: -20 C to +60 C
- Weight: Approximately 1.0 kg (2.2 lbs)
Applications
- Supervision of 1- or 2-stage gas or oil burners in commercial and industrial heating systems
- Forced draft burners for liquid or gaseous fuels in accordance with EN 267 and EN 676
- Integration into gas trains and boiler control systems requiring precise electronic ratio control
- High-demand intermittent burner operations in HVAC, thermal processing, and steam generation plants
- Use in systems requiring ionization probe or UV flame detection (with AGQ3 ancillary unit)


Reviews