Overview
The Siemens LGK16.635A27 is a high-performance, electronic burner control unit designed for the supervision and control of gas, oil, or dual-fuel forced draft burners. Engineered for medium to high-capacity applications, this flame safeguard is specifically built for continuous operation, making it ideal for industrial and commercial combustion plants. It features a self-checking flame signal amplifier that continuously monitors the burner’s safety, initiating a lockout in the event of a missing flame signal or a fault within the detection system. Its robust design allows it to replace legacy LFL1 series controls in existing installations, provided compatible flame detectors are used.
Features
- Self-checking flame supervision circuit detects faults in the detector, cables, or signal amplifier
- Supports multistage or modulating burner configurations for precise combustion control
- Integrated air pressure supervision ensures the air damper is in the correct position before and during operation
- Designed for continuous operation (more than 24 hours) or high-demand intermittent cycles
- Plug-in design allows for easy installation and maintenance using a dedicated baseplate
- Status and lockout indicator lamps provide immediate visual feedback for troubleshooting
- Compatible with QRA53 and QRA55 UV flame detectors or ionization probes
Specifications
- Model: LGK16.635A27
- Operating Voltage: AC 220 V to 240 V (50/60 Hz)
- Pre-purge Time (t1): 66 seconds
- Safety Time (TSA): 2.5 seconds
- Pre-ignition Time (t3): 5 seconds
- Post-purge Time: 15 seconds
- Protection Rating: IP40 (when installed)
- Weight: Approximately 0.94 kg (2.07 lbs)
- Operating Temperature: -20 C to +60 C
- Service Life: 250,000 startup cycles (approx. 10 years)
Applications
- High-capacity gas, oil, and dual-fuel forced draft burners
- Continuous operation heating systems in commercial and industrial settings
- Steam boilers and flash-steam generators requiring high safety standards
- Multi-boiler plants using sequencing where burners may operate for extended periods
- Direct-fired air heaters and industrial thermal process plants
- Retrofitting existing LFL1-based burner control systems to meet modern safety regulations