Overview
The Fireye EP200S is a specialized programmer module designed for use with the Flame-Monitor Burner Management Control System (E110 and E100 chassis). This microprocessor-based module provides essential start-up programming, safe-start checks, and continuous flame monitoring supervision for industrial and commercial burners. It is engineered to ensure the safe and efficient operation of combustion systems by managing the sequencing of the burner/blower motor, ignition, and fuel valves. A key feature of the EP200S is its support for multiple languages, specifically including Spanish, to accommodate diverse operating environments.
Features
- Selectable Purge Timing: Allows for a minimum of 30 seconds, with extended timings configurable via internal dipswitches.
- Trial for Ignition (TFI): Features selectable TFI periods to match specific burner requirements.
- Recycle Operation: Designed to initiate a recycle sequence rather than an immediate safety lockout if running interlocks open at specific points in the cycle.
- Modulation Control: Supports a modulator (firing rate motor) circuit for precise control of the burner’s firing rate.
- Connectivity: Equipped with an RJ45 connector for interfacing with ED510 alpha-numeric displays and two RJ-style connectors for E500 communication interfaces.
- Running Interlock Monitoring: Continuously monitors limit switches, airflow switches, and fuel pressure switches through the 3-P circuit.
- Non-Volatile Memory: Stores burner cycle and on-time history, accessible for diagnostics and maintenance.
Specifications
- Model: EP200S
- Supply Voltage: 120 VAC (typically used with EB700 chassis)
- Flame Failure Response Time (FFRT): 4 seconds (standard)
- Operating Temperature Range: -40 degrees F to 140 degrees F (-40 degrees C to 60 degrees C)
- Language Support: Spanish
- Shipping Weight: Approximately 2 lbs (0.9 kg)
- Dimensions: Approximately 2 x 2 x 2 inches
- Configuration: Six (6) side-mounted dipswitches for operational settings
Applications
The EP200S is ideally suited for industrial and commercial burner management systems that utilize automatically ignited oil, gas, or combination fuel burners. It is specifically designed to be used as a component of the Fireye Flame-Monitor system. Common applications include large-scale boilers, furnaces, and heaters where sophisticated sequencing and safety interlocking are required to maintain safe combustion conditions. It is also used as a replacement or upgrade for older programmer modules, offering backward compatibility with legacy displays like the ED500.