Overview
The Fireye EP100F is a specialized microprocessor-based programmer module designed for use with the FLAME-MONITOR Burner Management Control System. This specific model is tailored for the French-speaking market, featuring French language labels or documentation. As the central intelligence of the flame safeguard system, it provides essential start-up programming, safe-start checks, and continuous flame monitoring supervision for industrial and commercial burners. It is engineered to ensure high-fire prepurge and low-fire start positions are proven before ignition, enhancing operational safety and efficiency.
Features
- French language interface for localized application and compliance.
- Selectable prepurge timing through on-board dipswitches to meet specific burner requirements.
- Selectable Trial for Ignition (TFI) timing to optimize burner start-up sequences.
- Non-recycle operation mode that initiates a safety lockout upon flame failure or failure to ignite.
- Microprocessor-based design for precise timing and reliable diagnostic capabilities.
- Backward compatibility with older Fireye ED500 displays and modern ED510 alphanumeric displays.
- Integrated RJ45 and RJ-style connectors for communication interfaces and remote displays.
- Non-volatile memory to store burner cycle history and lockout information.
Specifications
- Manufacturer: Fireye
- Model Number: EP100F
- Product Type: Programmer Module
- Language: French
- Supply Voltage: 120 VAC (102 min, 132 max), 50/60 Hz
- Power Consumption: 12 VA
- Operating Temperature: -40 degrees F to 140 degrees F (-40 degrees C to 60 degrees C)
- Flame Failure Response Time (FFRT): 4 seconds maximum
- Dimensions: Approximately 6.5 x 9.4 x 2.45 inches
- Shipping Weight: Approximately 2.5 lbs to 3 lbs
Applications
The Fireye EP100F is used with Fireye E100 and E110 FLAME-MONITOR chassis in commercial and industrial combustion systems. It is ideally suited for automatically ignited oil, gas, and combination fuel burners that require French language support. It is commonly found in heating and process equipment such as boilers, furnaces, and ovens where comprehensive burner sequencing and safety monitoring are critical. The module is suitable for intermittent operation where the burner is expected to cycle at least once every 24 hours to ensure a safe-start check.



Reviews
There are no reviews yet.