Overview
The Fireye BP110UVFR-S1M is a compact, microprocessor-based BurnerPRO single burner flame safeguard control system. Designed for commercial heating and process equipment, it provides integrated burner sequencing, ignition, and continuous flame monitoring. This specific model features built-in Modbus communication and Series 1 timings. It is engineered as a functional drop-in replacement for Siemens LFL series controls, allowing for easy upgrades while utilizing existing wiring bases.
Features
- Dual-amplifier design supporting both UV non-self-check scanners and flame rod (FR) detection for application flexibility.
- Integrated Modbus RTU communication for remote monitoring and system integration.
- Eight “Smart” LEDs provide real-time diagnostic information and clear lockout codes for simplified troubleshooting.
- Non-volatile lockout capability ensures safety status is maintained even after a power loss.
- Run/Check feature allows operators to pause the program sequence in various positions (Purge, Ignition, PTFI, MTFI) for system testing.
- Built-in functions for air-flow proving, fuel valve proof of closure (POC), and optional valve proving.
- High-capacity relay contacts and a rugged IP40-rated housing for industrial reliability.
Specifications
- Supply Voltage: 110 VAC (+20%, -15%) at 50/60 Hz.
- Power Consumption: 7 VA.
- Timing Series: Series 1 timings.
- Operating Temperature: -40 degree F to 140 degree F (-40 degree C to +60 degree C).
- Storage Temperature: -58 degree F to 185 degree F (-50 degree C to +85 degree C).
- Humidity: 90% R.H. non-condensing.
- Protection Category: IP40.
- Flame Failure Response Time (FFRT): 1 second.
- Weight: Approximately 2.5 lbs (1.13 kg).
- Compatibility: Designed for use with 60-2981-1 wiring bases and compatible with Siemens LFL bases.
Applications
The BP110UVFR-S1M is ideally suited for commercial and industrial gas and oil burners. It is commonly used in boiler rooms, heating systems, and process heating applications where reliable flame safeguard is critical. Its design is particularly effective for retrofitting existing systems using Siemens LFL controls or Honeywell 7800 series units. Because it uses a non-self-checking UV amplifier, it is intended for non-permanent operations where the burner cycles at least once every 24 hours.