Overview
The Fireye BP110UVFR-S1 BurnerPRO is a compact, microprocessor-based integrated burner management control designed to provide reliable burner sequencing, ignition, and continuous flame monitoring. It is engineered for on-off, multi-stage, or modulating burners used in commercial heating and process equipment. This specific model features two built-in amplifiers, allowing for ultraviolet (UV) or flame rod (FR) detection, and is designed to operate on 110VAC with Series 1 timings. It is highly compatible, serving as a direct replacement for Siemens LFL series controls when used with the appropriate wiring base.
Features
- Integrated UV and FR amplifiers for application flexibility.
- Seven SMART LEDs provide real-time operating status and diagnostic lockout information.
- Non-volatile microprocessor control ensures safety and sequence integrity.
- Safety self-test performed on every start-up to detect premature flame or system faults.
- High-capacity relay contacts for direct control of burner components.
- Run/Check feature allows for manual stopping of the program sequence for troubleshooting.
- Remote and local reset capabilities.
- IP40 protection rating for the control housing.
Specifications
- Supply Voltage: 110 VAC (+20%, -15%), 50/60 Hz.
- Power Consumption: 7 VA.
- Operating Temperature: -40 degree C to +60 degree C (-40 degree F to 140 degree F).
- Relative Humidity: 90% RH non-condensing.
- Flame Detection: Compatible with UV90L, UV1AL, and UV5 scanners (non-self-check) or 69ND1 ionization rods.
- Timings: Series 1 factory-set firmware timings.
- Dimensions: 4.0 x 4.0 x 4.4 inches (without base).
- Compatibility: Compatible with 60-2981-1 and Siemens LFL series wiring bases.
Applications
The BP110UVFR-S1 is ideally suited for commercial and industrial combustion systems firing either oil or gas fuels. It is commonly used in boiler operations, kiln firing, and various heat treatment processes. When used as a UV control, it is intended for non-permanent operations requiring a burner recycle at least once every 24 hours. When utilized with a flame rod for FR detection, it can support permanent operation. It is frequently employed as a modern, reliable upgrade for aging electro-mechanical flame safeguard controls.