Flow,Mag,2″,H-rubb,4-20mA/Freq/Modbus
Electromagnetic Flow Meter, 2 in Flange, mA, Freq, Modbus
SPECIFICATIONS
| Amplifier | : | Meter Mount |
| Application | : | Flow |
| Communication Protocol | : | Modbus RTU |
| Display Type | : | LCD |
| Field Programmable | : | Yes |
| Fitting Material | : | Steel | Rubber |
| Fitting Size | : | 2″ |
| Fitting Type | : | Flange |
| Flow Measurement Accuracy | : | ±0.2% |
| Flow Measurement Range | : | 0.1 – 39.4 ft/s (0.03 – 12 m/s) |
| Flow Measurement Repeatability | : | ±0.1% |
| Flow Sensor Type | : | Electromagnetic |
| IP Protection | : | IP66 (NEMA 4) |
| Liner Material | : | Hard Rubber |
| Measurement Type | : | Flow |
| Medium | : | Water based liquids |
| Operating Fluid Temperature | : | 32 – 178 °F (0 – 80 °C) |
| Operating Temperature | : | 32 – 178 °F (0 – 80 °C) |
| Output Specifications | : | 4 – 20 mA | 0 – 20 mA | 0 – 10 mA | 2 – 10 mA | 1 ms – 1.1 s Scaled Pulse |
| Outputs | : | Analog output | Pulse output |
| Pipe Material | : | Copper | Polymer | Steel | Stainless Steel |
| Product Type | : | Sensor |
| Range | : | M2000 ModMAG Series |
| Totalizer Quantities | : | 2 |
| Totalizer Resettable | : | Yes |
| Warranty | : | 1 year |
FEATURES
Electromagnetic (mag) flow meters are capable of measuring flow in almost any liquid, slurry or paste with a minimum of electrical conductivity using Faraday’s law of induction. These meters are highly accurate, at 0.25% or better, exceeding AWWA accuracy standards for mechanical meters. The smart, micro-processor based electronics are simple to operate, with AMR and SCADA ready standard outputs. The NEMA 4X enclosure provides durability.
- Reliable, durable design – open flow tube design, no head loss, no moving parts to fail
- 0.25% accuracy independent of fluid viscosity, density, and temperature
- Bi-directional flow measurement capability, suitable for inter-city billing
- Password security – protect against unwanted program changes
- Wide flow range – exceeds operating characteristics of turbine and propeller meters
- Works with most solids common in liquid systems, great for well water and reclaimed water systems, not fouled by sand, gravel, or debris
- Flow direction – uni-directional or bidirectional, two separate totalizers (programmable)
- Coil power – pulsed DC
- 4 to 20 mA, 0 to 20 mA, 0 to 10 mA, 2 to 10 mA (programmable and scalable); voltage sourced 24 VDC (isolated); maximum loop resistance less than 800 Ohm analog outputs
- Four total, configurable 24 VDC sourcing active output (up to two), 100 mA total, 50 mA each; sinking open collector output (up to four), 30 VDC maximum, 100 mA each; AC solid-state relay (up to two), 48 VAC, 500 mA maximum digital outputs
- Scalable up to 10 kHz, passive open collector up to 10 kHz, active switched 24 VDC, up to two outputs (forward and reverse) pulse width programmable from 1 to 1100 ms or 50% duty cycle pulse outputs



Reviews