Overview
The Fireye 45RM4-1001CEX is a discontinued, high-performance infrared (IR) self-checking flame scanner designed for industrial burner management and flame safeguard applications. This specific model features a Cenelec EExd IIC explosion-proof housing, making it suitable for hazardous environments. It is engineered to detect the presence or absence of flames by monitoring specific flame flicker frequencies, providing high discrimination in multi-burner environments. While the 45RM4 series has been withdrawn from production, it is officially replaced by the Fireye InSight II Type 95DSS3-1CEX integrated scanner.
Features
- Infrared (IR) sensing technology using a solid-state lead sulphide detector with a range of 700 to 2,500 nm.
- Electronic self-checking for continuous operation and failsafe performance.
- 16-position frequency filter selector switch (30 to 180 Hz) to optimize flame discrimination and ignore background radiation.
- Adjustable gain control via a rear-mounted potentiometer to fine-tune sensitivity.
- 10-LED flame strength indicator on the back of the scanner for real-time diagnostics.
- Explosion-proof housing rated EExd IIC T6 and IP66 for use in volatile industrial settings.
Specifications
- Model Number: 45RM4-1001CEX
- Housing Material: Die-cast aluminum explosion-proof enclosure
- Power Requirements: 24V DC provided by a compatible Fireye amplifier
- Mounting: 1-inch BSP mounting flange (included p/n 35-128 or 35-130)
- Operating Temperature: -13°F to 150°F (-25°C to 65°C)
- Humidity: 0% to 95% R.H. non-condensing
- Purge Air: Required at 4.0 SCFM minimum to keep the lens clean and cool
- Weight: Approximately 7.6 lbs (3.5 kg)
Applications
The 45RM4-1001CEX is primarily used for monitoring flames from “dirty” fuels such as pulverized coal, oil, and gas in large industrial boilers and furnaces. It is designed to work in conjunction with Fireye 25SU3-5166, 25SU3-5168, and 25SU3-2000 amplifiers. Due to its explosion-proof rating, it is ideal for petrochemical plants, refineries, and power generation facilities where hazardous gases or dusts may be present. For modern installations or replacements, the 95DSS3-1CEX is recommended as it integrates the scanner and amplifier into a single unit.



Reviews
There are no reviews yet.