The Fireye YP113 is a microprocessor-based programmer module designed for use with the BurnerLogix burner management control system. It provides essential sequencing, timing, and safety monitoring for automatically ignited oil, gas, and combination fuel burners. This module is specifically required for systems needing CE regulatory approval and features a compact footprint that simplifies installation in industrial and commercial combustion environments.
Features
- Keypad selectable parameters allow users to customize operational settings via an external display module.
- Non-recycle operation prevents the system from automatically restarting after a safety lockout.
- Open and closed damper proving verifies the position of the air damper before and during the purge sequence.
- Modulation support enables the control of firing-rate circuits for precise process heating.
- Integrated Run/Check switch allows operators to stop the program sequence in specific positions for testing and commissioning.
- RS-485 Modbus communications for integration into building management or industrial control systems.
Specifications
- Model Number: YP113
- Compatibility: Fireye BurnerLogix (YB110, YB230, ZB110, ZB230 chassis)
- Flame Failure Response Time (FFRT): 1 second
- Trial for Ignition (TFI) Time: Fixed
- Low Fire Start Time: 10 seconds
- Operating Temperature: -40 degrees Fahrenheit to 140 degrees Fahrenheit (-40 degrees Celsius to 60 degrees Celsius)
- Power Consumption: 25 VA
- Regulatory Compliance: Required for CE applications
Applications
The YP113 is used in industrial and commercial burner control systems to manage the sequencing and safety of combustion equipment. It is ideally suited for applications requiring precise modulation and rigorous safety protocols, such as steam boilers, large furnaces, and hot water heaters. Its interchangeable design allows facilities to easily upgrade their burner management systems as application requirements change.