Overview
The Johnson Controls VG1841AG+9A4IGA is a high-performance valve and actuator assembly consisting of a 1/2-inch, three-way forged brass ball valve and a VA9104-AGA-2S non-spring-return electric actuator. Designed to regulate the flow of hot or chilled water, this pre-assembled unit offers robust environmental control and precise modulation in response to demand from building automation controllers. It features an integrated characterized disk to achieve precise, predictable flow characteristics, minimizing wear and maximizing stability.
Features
- High Rangeability: Offers a high 500:1 rangeability to ensure exceptional temperature control under variable load conditions.
- Durable Forged Brass Body: Built to withstand demanding commercial operations with a high static pressure rating.
- Characterized Insert: Features an integrated disk providing an equal percentage flow characteristic on the in-line port and linear on the bypass port.
- Reliable Seal Technology: Employs graphite-reinforced PTFE seats and double EPDM O-ring stem seals for leak-free performance verified for over 200,000 cycles.
- Maintenance-Free Actuation: Utilizes a direct-coupled, non-spring-return electric actuator designed for reliable long-term service without specialized adjustment.
Specifications
- Valve Size: 1/2 inch (DN15)
- Body Pattern: 3-way mixing or diverting
- Flow Coefficient (Cv): 4.7 CV
- Connection Type: Female NPT threaded end connections
- Trim Material: Plated brass ball and stem
- Closeoff Pressure: 200 psi
- Maximum Static Pressure Rating: 580 psig (PN40)
- Maximum Recommended Pressure Drop: 50 psid
- Fluid Temperature Range: 23°F to 203°F (-5°C to 95°C)
- Actuator Model: VA9104-AGA-2S
- Actuator Type: Electric, Non-Spring Return (NSR)
- Control Signal: Floating (On/Off without timeout; requires controller timeout protection)
- Supply Voltage: 24 VAC
Applications
- Commercial HVAC systems for precision temperature control of chilled water, hot water, and up to 50% glycol solutions.
- Fan coil units, unit ventilators, and air handling terminal equipment requiring variable load modulation.
- Hydronic heating and cooling systems integrated into building automation system (BAS) networks.
- Zoning applications requiring dependable 3-way mixing or diverting flow regulation.