Overview
The Johnson Controls VG1245AD+9A4GGA is a factory-assembled 1/2-inch, 2-way characterized ball valve paired with a VA9104-GGA-2S non-spring-return electric actuator. Designed to regulate the flow of hot water, chilled water, or low-pressure steam in commercial Heating, Ventilating, and Air Conditioning (HVAC) systems, this assembly responds precisely to signals from a system controller. It features high-quality stainless steel trim within a durable forged brass body to ensure exceptional performance, accurate control, and a long operational lifespan.
Features
- Long Life Expectancy: Tested and rated to operate reliably for a minimum of 200,000 leak-free cycles, even in challenging iron-oxide contaminated water conditions.
- Proportional Control: Equipped for precise positioning via a 0-10 VDC (or 2-10 VDC) proportional analog input signal.
- High Rangeability: Offers a 500:1 rangeability that ensures highly accurate flow control under varying load demands.
- Advanced Seating & Seals: Utilizes 15% graphite-filled PTFE seats backed with EPDM O-rings for constant seating force, alongside an EPDM double O-ring stem seal for superior leak protection.
- Characterized Flow: Includes an Amodel flow characterizing disk to achieve an equal percentage flow characteristic, providing stable temperature management.
Specifications
- Valve Size & Pattern: 1/2 inch, 2-Way
- Connection Type: Female NPT (National Pipe Thread)
- Flow Coefficient (Cv): 1.2 Cv
- Actuator Type: Electric, Non-Spring Return (VA9104 Series)
- Supply Voltage: 24 VAC (Nominal)
- Input Control Signal: 0(2) to 10 VDC Proportional
- Position Feedback: 0(2) to 10 VDC
- Actuator Torque: 35 lb-in (4 Nm)
- Runtime: 60 seconds
- Static Pressure Rating: 580 psig (PN40)
- Maximum Close-Off Pressure: 200 psid
- Maximum Pressure Drop: 50 psid
- Materials of Construction: Forged brass body, 300 Series stainless steel ball and stem, graphite-reinforced PTFE seats, EPDM O-ring seals, and a PTFE thermal spacer.
- Auxiliary Switch: No switch included
Applications
- Commercial HVAC Systems: Primarily used for regulating hot water and chilled water delivery within building automation architectures.
- Hydronic Control: Ideal for managing fluid flow in fan coil units, unit ventilators, reheat coils, and various hydronic heating or cooling loops.
- Glycol Systems: Suitable for systems requiring temperature regulation utilizing glycol solutions up to 50%.
- Low-Pressure Steam: Designed to handle low-pressure saturated steam applications up to 15 psi due to its durable stainless steel trim configuration.



Reviews