Overview
Microprocessor-based integrated primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls.
Features
- Functions include automatic burner sequencing, flame supervision, system status indication, system or self diagnostics and troubleshooting.
- Subbase, amplifier, and prepurge timer are required for operation.
- Options include 2 line VDF keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, and 4-LINE LCD keyboard display module.
- Five LEDs provide sequence information.
- Interchangeable plug-in flame amplifiers.
- Optional remote annunciation of operation and fault information.
- Nonvolatile memory retains history files and sequencing status after power loss.
- Optional remote reset capability.
- Optional report generation. Selectable relight or lockout on loss of flame.
- Airflow switch check.
Product Specifications
| Application | On-Off Primary Control with Prepurge |
| Dimensions (in.) | 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase |
| Dimensions (mm) | 127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase |
| Used With | R7847 only |
| Weight (lb) | 1 lb 15 oz |
| Weight (kg) | 0.9 kg |
| Comments | Higher Flame Sensor Voltage for Infra Red Heater Applications |
| Frequency | 50 Hz; 60 Hz (±10%) |
| Approvals, Underwriters Laboratories Inc. | Component Recognized, File No. MP268; Guide No. MCCZ. |
| Approvals, Canadian Standards Association | Certified, File No. LR95329-3. |
| Voltage | 120 Vac (+10, -15%) |
| Shipping and Storage Temperature Range (F) | -40 F to +140 F |
| Shipping and Storage Temperature Range (C) | -40 C to +60 C |
| Approvals, Federal Communications Commission | FCC Part 15, Class B, Emissions. |
| Flame Establishing Period – Pilot | 15 sec or 30 sec |
| Flame Establishing Period – Main | Intermittent |
| Interlocks | Selectable |
| PrePurge | Determined by ST7800A Purge Timer Card |
| Required Components | Q7800A,B Universal Wiring Subbases. R7847, R7848, R7851,or R7852 Flame Signal Amplifier. |
| Delayed Main Valve | No |
| Pilot Type | intermittent |
| Vibration | 0.5 G environment |
| Approvals, Control Safety Devices | Acceptable: CSD-1 |
| Approvals, Swiss RE | Acceptable |
| Approvals, Factory Mutual | Report No. OX4A5.AF. |