Overview
Microprocessor-based integrated primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls.
Features
- Functions include automatic burner sequencing, flame supervision, system status indication, system or self diagnostics and troubleshooting.
- Subbase, amplifier, and prepurge timer are required for operation.
- Options include 2 line VDF keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, and 4-LINE LCD keyboard display module.
- Five LEDs provide sequence information.
- Interchangeable plug-in flame amplifiers.
- Optional remote annunciation of operation and fault information.
- Nonvolatile memory retains history files and sequencing status after power loss.
- Optional remote reset capability.
- Optional report generation. Selectable relight or lockout on loss of flame.
- Airflow switch check.
Product Specifications
|
Application |
On-Off Primary Control |
|
Dimensions (in.) |
5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase |
|
Dimensions (mm) |
127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase |
|
Weight (lb) |
1 lb 13 oz |
|
Weight (kg) |
0.8 kg |
|
Frequency |
50 Hz; 60 Hz (±10%) |
|
Approvals, Underwriters Laboratories Inc. |
Component Recognized, File No. MP268; Guide No. MCCZ. |
|
Approvals, Canadian Standards Association |
Certified, File No. LR95329-3. |
|
Voltage |
120 Vac (+10, -15%) |
|
Shipping and Storage Temperature Range (F) |
-40 F to +140 F |
|
Shipping and Storage Temperature Range (C) |
-40 C to +60 C |
|
Approvals, Federal Communications Commission |
FCC Part 15, Class B, Emissions. |
|
Flame Establishing Period – Pilot |
30 sec fixed |
|
Flame Establishing Period – Main |
Intermittent |
|
Required Components |
Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. |
|
Pilot Type |
intermittent |
|
Vibration |
0.5 G environment |
|
Approvals, Swiss RE |
Acceptable |
|
Approvals, Factory Mutual |
Report No. OX4A5.AF. |
024 37040 000 York Contactor
019165F Raypak PIM Control
HM700ACYL2 Honeywell Steam Cylinder
HD46AR265 Carrier Blower Motor
025 53141 000 York Temperature Sensor
SQM41.261A21 Siemens Actuator
ATV320U22N4C Schneider Electric Variable Frequency Drive
K3A551V Asco Gas
Shutoff Valve
CB201 / R201 First Company Control Board – OEM Original Board 

Reviews
There are no reviews yet.