RM7824A2006 Honeywell Burner Control Datasheet
Overview
The Honeywell RM7824A2006 is a primary ON/OFF burner control module from the Honeywell RM7800 Series. This 24VDC control provides dependable flame safeguard protection for burners used in commercial and industrial applications. It performs burner sequencing, flame supervision, system safety checks, and automatic shutdowns in unsafe conditions.
Designed for durability and serviceability, the RM7824A2006 integrates with the Q7800 subbase and other RM7800 modules to provide a reliable, modular flame safeguard system. Its microprocessor-based design ensures precise performance, reduced downtime, and fast troubleshooting through built-in LED diagnostics.
Features
-
Primary ON/OFF burner control operating on 24VDC
-
Microprocessor-based flame safeguard with system diagnostics
-
LED indicators for real-time system status and troubleshooting
-
Plug-in modular design for easy replacement and installation
-
Monitors limits, interlocks, and flame signal strength
-
Ideal for boilers, furnaces, ovens, and process heating systems
-
Proven Honeywell reliability for long-term system safety
Specifications
| Part Number | RM7824A2006 |
| Application | Primary Control 24 Vdc |
| Dimensions (in.) | 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase |
| Dimensions (mm) | 127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase |
| Weight (lb) | 1 lb 13 oz |
| Weight (kg) | 0.8 kg |
| Approvals, Underwriters Laboratories Inc. | Component Recognized, File No. MP268; Guide No. MCCZ. |
| Approvals, Canadian Standards Association | Certified, File No. LR95329-3. |
| Voltage | 24 Vdc (+10, -15%) |
| Shipping and Storage Temperature Range (F) | -40 F to +140 F |
| Shipping and Storage Temperature Range (C) | -40 C to +60 C |
| Approvals, Federal Communications Commission | FCC Part 15, Class B, Emissions. |
| Flame Establishing Period – Pilot | 4 sec or 10 sec |
| Flame Establishing Period – Main | Intermittent |
| Required Components | Q7800A,B Universal Wiring Subbases. R7824 or R7848 Flame Signal Amplifier. |
| Pilot Type | intermittent |
| Vibration | 0.5 G environment |
| Approvals, Swiss RE | Acceptable |
| Approvals, Factory Mutual | Report No. OX4A5.AF. |
Applications
The RM7824A2006 Honeywell Burner Control is used in a wide range of combustion management systems requiring safe and automatic burner sequencing. Typical applications include:
-
Commercial and industrial boilers
-
Process heaters and furnaces
-
Kilns and ovens
-
Industrial drying systems
This controller ensures safe burner ignition, flame supervision, and automatic shutdown to protect equipment and personnel.
Benefits
-
Reliable flame safeguard protection
-
Modular design for quick service and replacement
-
Compatible with RM7800 system architecture
-
Advanced diagnostic feedback reduces troubleshooting time
-
Designed for demanding industrial environments



Reviews
There are no reviews yet.