Overview
The Fireye 45UV5-1000EX is a self-checking ultraviolet (UV) flame scanner integrated into a heavy-duty, explosion-proof housing. Designed for high-reliability industrial applications, this unit detects UV radiation emitted by fossil fuel flames such as natural gas, propane, and diesel. The “EX” designation indicates the inclusion of a NEMA 7 rated enclosure, making it suitable for hazardous locations where flammable gases or dusts may be present. It features an internal electromagnetic shutter that provides continuous self-checking of the scanner’s internal components and signal circuits, ensuring fail-safe operation in continuous-firing burner environments.
Features
- Self-Checking Technology: Integrated electromagnetic shutter periodically interrupts the UV path to verify proper sensor and circuit operation.
- Explosion-Proof Enclosure: NEMA 7 rated housing designed for Class 1, Div 1 & 2 (Groups C, D) and Class 2, Div 1 & 2 (Groups E, F, G) hazardous environments.
- High Sensitivity Optics: Features a planoconvex quartz lens that increases UV sensitivity by up to 400 percent compared to standard windows.
- Durable Construction: Cast aluminum housing sealed with high-temperature, oil-resistant gaskets for protection in harsh industrial settings.
- Easy Maintenance: Hinged mount design allows for quick access to clean the quartz lens without complete disassembly.
- Purge Air Connection: Includes a 3/8 inch NPT threaded connection for cooling and cleaning the lens with purge air.
Specifications
- Model Number: 45UV5-1000EX
- Sensing Type: Ultraviolet (UV) radiation (2200 to 2600 angstroms)
- Housing Rating: NEMA 7, 9; Class I, Div. 1 & 2, Groups C, D; Class II, Div. 1 & 2, Groups E, F, G
- Mounting: 1 inch NPT threaded sight pipe connection
- Operating Temperature: -40°F to 200°F (-40°C to 93°C)
- Weight: Approximately 18 lbs (8.2 kg)
- Compatible Controls: Fireye Flame-Monitor, BurnerLogix, D-Series, FlameWorx, and MicroM
- Dimensions: Approximately 8.5 inches in length and 4 inches in width (scanner unit)
Applications
The 45UV5-1000EX is primarily used for flame failure protection in single and multi-burner industrial applications. It is ideal for electric utility boilers, power boilers, large furnaces, and incinerators that operate continuously. It is specifically designed for use in hazardous areas where explosion-proof equipment is mandated. This scanner is highly effective at monitoring flames from natural gas, coke oven gas, propane, methane, butane, kerosene, and light petroleum distillates. In multi-burner setups, it is used to discriminate between the target burner flame and background radiation from adjacent burners.