Overview
The Johnson Controls TEC3622-14-000 is a networked thermostat controller from the TEC3000 Color Series. It is designed to provide wireless, stand-alone, or field-selectable BACnet MS/TP or N2 networked control for commercial building automation systems. This model features a full-color backlit touchscreen user interface, support for dehumidification, a white enclosure, and includes the JCI logo. It features non-volatile programming memory and a USB port that allows for rapid configuration cloning between identical units to simplify installation.
Features
- Field-selectable BACnet MS/TP or N2 networked communication for easy integration and system upgrading.
- Configurable touchscreen user interface with a backlit full-color liquid crystal display (LCD).
- USB port configuration for simple backup, restore, and rapid cloning of settings between units.
- Dedicated dehumidification capabilities for compatible HVAC equipment types.
- Two configurable binary inputs and two or three configurable analog inputs for advanced monitoring functions (e.g., filter alarms, window status).
- Support for multiple fan configurations and compatibility with a full line of remote TE-6300 Series temperature sensors.
- Integral humidity sensor included on this model series.
Specifications
- Supply Voltage: 19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal (Class 2 or SELV).
- Communication Interface: Field-selectable BACnet MS/TP or N2.
- Control Outputs: 0 to 10 VDC proportional fan coil and zoning control.
- Analog Output Rating: 0 to 10 VDC into 2k ohm minimum resistance.
- Relay Contact Rating: 19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush.
- Temperature Control Range: Heating: 40.0°F to 90.0°F (4.5°C to 32.0°C); Cooling: 54.0°F to 100.0°F (12.0°C to 38.0°C).
- Temperature Accuracy: +/- 0.9°F (+/- 0.5°C) typical calibrated at 70°F.
- Humidity Accuracy: +/- 5% RH from 20% to 80% RH.
- Ambient Operating Conditions: 32°F to 122°F (0°C to 50°C); 95% RH maximum, non-condensing.
- Enclosure Color: White with JCI Logo.
Applications
- Local hydronic reheat valves and pressure-dependent VAV equipment with or without local reheat.
- Two-pipe or four-pipe fan coils, cabinet unit heaters, and associated commercial zoning systems.
- Single- or two-stage control of unitary rooftop units (RTUs) and heat pumps, including models equipped with economizers.
- High-energy usage commercial environments such as schools, hotels, and offices requiring centralized building automation system remote monitoring.