Overview
The Johnson Controls TE-6316P-1 is a flexible duct averaging temperature sensor designed for HVAC systems and Building Automation Systems (BAS). Featuring a 17-foot nickel sensing element, it delivers a true average temperature reading across large cross-sections such as mixed-air plenums and large air handling units, where single-point measurements are insufficient. The sensor is housed in a durable plastic enclosure that provides excellent mechanical protection and simplifies field wiring.
Features
- Flexible 17-foot averaging probe for accurate mean temperature measurement across large ducts and plenums
- Highly stable and robust 1k ohm nickel active sensing element for long service life
- Rigid thermoplastic enclosure provides code-friendly, durable wiring termination
- Complete assembly packaged with necessary mounting accessories to simplify ordering and reduce installation cost
Specifications
- Sensor Type: 1000 Ohm Nickel RTD @ 70°F (21°C)
- Probe Length: 17 feet (5.2 meters)
- Probe Material: Flexible copper capillary
- Accuracy: ± 0.34°F (± 0.19°C) at 70°F
- Temperature Range: -50° to 220°F (-46° to 104°C)
- Output Signal: Resistance, passive 2-wire
- Enclosure Material: Plastic / PVC conduit box
Applications
- Commercial air handling unit (AHU) mixed-air temperature sensing
- Large HVAC duct temperature averaging
- Building Automation Systems (BAS) environmental monitoring
- Commercial and institutional plenum airflow temperature profiling


Reviews