Overview
The Honeywell RM7830A2029 is a microprocessor-based integrated programming burner control designed for ON/OFF power burners using 120 VAC. It supports full burner sequencing, flame supervision, diagnostics, and includes a 30-second postpurge feature for safe shutdown. Built for industrial and commercial combustion systems, it retains fault history in non-volatile memory and uses LED status indicators for troubleshooting.
This model is designed for use with subbase, amplifier, and purge timer modules for full operation. It meets European / CE timing standards and offers optional features like remote reset and reporting modules.
Features
-
ON/OFF primary burner control operating at 120 VAC
-
Microprocessor logic with complete self-diagnostics
-
Five LED indicators for sequence and fault status
-
Retains lockout and history information after power loss
-
Supports selectable pilot flame and main flame establishing periods
-
30-second postpurge cycle
-
Early spark termination (5 seconds)
-
Modular plug-in design with interchangeable amplifiers
-
Supports remote annunciation and reset capabilities
-
User-selectable airflow switch check and interlock support
Specifications
| Part Number | RM7830A2029 |
| Application | Programming Control |
| Dimensions (in.) | 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase |
| Dimensions (mm) | 127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase |
| Weight (lb) | 1 lb 10 oz |
| Weight (kg) | 0.7 kg |
| Comments | On/Off Power Burner |
| Frequency | 50 Hz; 60 Hz (±10%) |
| Voltage | 120 Vac (+10, -15%) |
| Shipping and Storage Temperature Range (F) | -40 F to +140 F |
| Shipping and Storage Temperature Range (C) | -40 C to +60 C |
| Approvals, Federal Communications Commission | FCC Part 15, Class B, Emissions. |
| Flame Establishing Period – Pilot | 3 sec or 5 sec |
| Flame Establishing Period – Main | 3 sec, or 5 sec, or Intermittent |
| Interlocks | Lockout |
| Preignition | Yes |
| PrePurge | Determined by ST7800A Purge Timer Card |
| PostPurge | 30 sec |
| Early Spark Termination | Yes, 5 sec |
| Required Components | Q7800A,B Universal Wiring Subbases. R7847, R7849, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. |
| AirFlow Check | User selectable |
| Second Stage Pilot Valve | Intermittent |
| Pilot Type | interrupted |
| Vibration | 0.5 G environment |
| Approvals, Swiss RE | Acceptable |
| Approvals, Factory Mutual | Report No. 1V9AO.AF. |
| Approvals, Gastec/European | GASTEC: CE-63AP3070/1, Approved to EN298. |
Applications
The RM7830A2029 is ideal for burner systems that require robust control and safety features, including:
-
Industrial boilers and furnaces
-
Process heaters and ovens
-
Packaged burner systems
-
Combustion systems using gas, oil, or combination fuels
It provides safe ignition sequencing, continuous flame monitoring, and automatic shutdown on fault detection.
Benefits
-
Integrated flame safeguard and sequencing in one module
-
Fast diagnostics via LEDs and memory retention
-
Modular design makes servicing and replacement easier
-
Compliant with international timing standards
-
Compatible with Honeywell’s RM7800 modular components



Reviews
There are no reviews yet.