UPC: 785901643128
Overview of SE8650U0B11 Schneider Electric Thermostat
The Schneider Electric SE8650U0B11 is a fully programmable thermostat designed for roof-top units and heat pump systems. Featuring integrated BACnet MS/TP communication, a relative humidity sensor, and indoor air quality (IAQ) control, this thermostat provides precise environmental management for commercial HVAC applications. The clean white fascia and backlit display make it both functional and professional for visible wall installations.
Roof Top Unit, Heat Pump & Indoor Air Quality Ctrl: BACnet MS/TP, RH sensor & control, White Case/Fascia
Product Alert: Must purchase communication module (VCM8000V5045P) separately for Zigbee Pro
Product Specifications
| [Us] rated supply voltage | 24 V AC 50/60 Hz +/- 15 % |
| Application | Staging equipment (RTU/HP) |
| AWG Gauge | AWG 22…AWG 18 |
| Brand | Schneider Electric |
| By Schneider | Yes |
| California proposition 65 | WARNING: Cancer and Reproductive Harm – www.P65Warnings.ca.gov |
| Color Casing | White |
| Communication Port Protocol | BACnet MS/TP |
| Modbus RTU | |
| Zigbee Pro | |
| Depth | 0.98 in (25 mm) |
| Device Short Name | SE8600 |
| Directives | 2014/30/EU – electromagnetic compatibility |
| 2014/35/EU – low voltage directive | |
| 2014/53/EU – radio equipment directive | |
| Economizer | No |
| Function Available | Available with CO2/RH/T |
| Brightness sensor | |
| Changes can be made directly over display | |
| Code lock function | |
| Easily configurable | |
| Fan control | |
| Firmware update by USB | |
| HVAC control | |
| Height | 4.72 in (120 mm) |
| Humidity Calibration Certificate | 1 pt |
| Humidity Control | Yes |
| Humidity Measurement Drift | Less Than 1 % Yearly |
| Humidity Setting Range | 30…95 % |
| Information Displayed | Temperature – 40…122 °F |
| Input Type | Analog 5 |
| Dry contact 2 | |
| Input Voltage | 0…10 V |
| Manufacturer | Schneider Electric |
| Market Segment | Buildings |
| Healthcare | |
| Lodging/Hotel | |
| Non-critical buildings | |
| Office | |
| Residential | |
| School | |
| Small commercial | |
| Measurement Accuracy | Humidity +/- 10 %, 10…20 % non-condensing) |
| Humidity +/- 10 %, 80…90 % non-condensing) | |
| Humidity +/- 5 %, 20…80 % RH non-condensing) | |
| Temperature +/- 0.5 °C, | |
| Net Weight | 11.99 oz (340 g) |
| Network Frequency | 50 Hz |
| 60 Hz | |
| Output Current | 0.3 A universal output |
| 1 A relay output | |
| 1.5 A universal output inrush) | |
| 3 A relay output inrush) | |
| Output Type | 4 universal |
| 5 relay output | |
| Output Voltage | 0…10 V AC/DC voltage output |
| 24 V AC/DC relay output | |
| PIR Cover | No |
| Product Name | SE8000 Series |
| Product Or Component Type | Roof top unit |
| Range | EcoStruxure Building Expert |
| Relative Humidity | 0…75 % |
| Scheduling | Yes |
| Sensor Type | Humidity: bulk polymer |
| Humidity: space RH sensor | |
| Temperature: 10 kOhm T2 NTC thermistor | |
| Standards | EN/IEC 60730-1 |
| ETSI EN 300 328 | |
| ETSI EN 301 489-1:v1.9.2 | |
| ETSI EN 301 489-17:v2.2.1, 2012 | |
| FCC part 15 subpart B | |
| FCC part 15 subpart C | |
| ICES-003 | |
| UL 60730-2-9 | |
| Surface Finish | Matt |
| Surface Treatment | Untreated |
| Temperature Ambient Operating Range | 32…122 °F (0…50 °C) |
| Temperature Resolution | 0.1 °C |
| Temperature Setting Range | 40…90 °F (4.5…32 °C) heating |
| 54…100 °F (12…37.5 °C) cooling | |
| Temperature Shipping and Storage Range | -22…122 °F (-30…50 °C) |
| Width | 3.39 in (86 mm) |
Key Features & Benefits
BACnet MS/TP Communication: Enables easy integration with building automation systems.
Built-in RH Sensor: Provides humidity control for optimal comfort and efficiency.
IAQ Control: Supports indoor air quality applications with optional CO₂ and fan control features.
Programmable Interface: Allows custom scheduling for energy savings and comfort.
Modern Design: White fascia complements any commercial or institutional setting.
TAA Compliant: Suitable for government and public sector installations.
Applications
Commercial HVAC systems (RTU or heat pump)
Office buildings, schools, and hospitals
Facilities requiring BACnet integration
Zones needing temperature and humidity control
Government or TAA-compliant projects
Installation & Maintenance
Mount on an interior wall approximately 5 ft (1.5 m) above the floor.
Connect power and communication wiring per manufacturer guidelines.
Configure via onboard menu or BACnet network.
Regularly clean the fascia and verify sensor calibration for optimal performance.




Reviews